Cover illustration for "How It Works: Timers": line drawing of a DIN-rail timer with a dial, a clock face and a pulse.

A timer, or time-delay relay, is a relay whose contacts change state a set time after something happens: a supply is switched on, a push button is pressed, a contact opens. Timers delay a motor start, keep a fan running after a burner stops, flash a warning light or switch a motor from star to delta. The hard part is rarely the setting itself; it is knowing exactly which event starts the timing and what the output does. This guide explains the common functions and how to identify the right timer when you replace one.

Supply, trigger and output

Three signals describe any timing function:

  • Supply (input voltage): the power applied to the timer's supply terminals (often A1-A2). For some functions, applying the supply is what starts the timing.
  • Trigger (control signal): a separate input, often marked B1 or S, used by functions that need the timer powered first and then started by another signal.
  • Output: a relay contact (often a changeover contact) or a solid-state output that switches the load. The timer does not power the load; the load circuit has its own supply.

Triggers come in two designs. A dry-contact trigger expects a voltage-free switch (push button, limit switch, float switch) between two timer terminals. A powered trigger expects a voltage on the trigger terminal. They are not interchangeable: applying voltage to a terminal designed for a dry contact can damage the timer. Check the wiring diagram printed on the timer or in its datasheet before connecting a trigger.

The common timing functions

On-delay (delay on make)

When the supply is applied, timing starts. At the end of the set time the output switches on and stays on as long as the supply remains. Removing the supply resets the timer and turns the output off at once. Typical uses: delaying the start of a second motor to limit inrush, or waiting for pressure to build before enabling a sequence.

Off-delay (delay on break)

With the timer powered, closing the trigger switches the output on immediately. When the trigger opens, timing starts, and the output switches off at the end of the set time. If the trigger closes again during timing, the timer resets. Typical uses: keeping a cooling fan or a conveyor running for a while after the main machine stops.

Some off-delay timers, often called true off-delay, need no trigger and no supply during the delay: they start timing when their supply is removed, using stored energy. They are handy where the control voltage itself disappears, but the maximum delay is usually limited. Check the datasheet.

Interval (interval on)

When the supply is applied, the output switches on at once and stays on for the set time, then switches off even though the supply is still present. Removing the supply resets it. Typical use: running a lubrication pump for a fixed time at each machine start.

One-shot (single shot)

The timer is powered; a momentary trigger switches the output on for the set time, whatever the trigger does next. It turns a short pulse into a pulse of known length, for example to drive a solenoid or a horn for a fixed time.

Repeat cycle (flasher)

The output alternates on and off for as long as the supply is applied. Some models start with the output on, others with it off, and many allow separate on and off times. Typical uses: flashing beacons, intermittent lubrication or agitation.

Star-delta timer

A dedicated timer for star-delta (wye-delta) motor starting. When the start command is given, the star contact closes and the motor runs up in star at reduced voltage. At the end of the set time the star contact opens, a short pause follows, and then the delta contact closes. The pause makes sure the star contactor has opened before the delta contactor closes, so the two can never be closed together. The pause is fixed or adjustable depending on the model.

Timing charts for on-delay, off-delay, interval, one-shot, repeat-cycle and star-delta timer functions, showing supply, trigger and output signals and the set time t.

Common timer functions at a glance.

Summary table

Function Timing starts when Output during timing Output after timing
On-delay Supply applied Off On until supply removed
Off-delay Trigger opens (timer powered) On Off
Interval Supply applied On Off
One-shot Trigger pulse (timer powered) On Off
Repeat cycle Supply applied Alternates on/off Continues until supply removed
Star-delta Start command Star contact closed Pause, then delta contact closed

For guidance only. Manufacturers use different names and letter codes for the same function; the timing chart in the datasheet is the reference.

Multifunction timers

Many DIN-rail timers offer several functions in one housing. A selector chooses the function, a second one chooses the time range (seconds, minutes, hours), and a dial sets the value within that range. They simplify spare-parts stock, but they are also a common source of trouble after a replacement: the function and range switches must be set to match the old timer, not left at the factory setting. Write down the settings of the timer you remove before you take it out.

Other forms of timer

  • Plug-in timers on 8-pin or 11-pin octal bases, still common on older panels. The base pinout must match.
  • Timer add-on blocks that clip onto a contactor, either electronic or, on older equipment, pneumatic.
  • PLC timers: in a PLC program the same functions exist as software instructions (in IEC 61131-3, for example, TON for on-delay, TOF for off-delay and TP for a pulse). When a hardwired timer is replaced by PLC logic, the function must be translated, not just the time value.

Replacing a timer: checklist

  1. Record the full part number, the supply voltage (AC, DC or universal) and the function letter or code.
  2. Note the dial and selector positions on the old timer.
  3. Check the trigger type (dry contact or powered) and the terminal markings.
  4. Check the output: number of contacts, changeover or not, and contact rating for the load.
  5. Check the mounting: DIN rail, panel, octal socket or contactor add-on.

Safety: work on electrical equipment must be done by qualified personnel following the applicable electrical code and the manufacturer's instructions.

Key takeaways

  • Know what starts the timing: the supply, or a separate trigger.
  • On-delay waits before turning on; off-delay waits before turning off.
  • Never put voltage on a trigger input designed for a dry contact.
  • On a multifunction timer, copy the function and range settings from the old unit.

Related parts at 3JIndustry

See our used timers and time-delay relays, along with relays and contactors. For the basics of relay operation, read How It Works: Relays.

Looking for a discontinued part? Send the full part number to sales@3jindustry.com or use our contact page.

Request a quote

Fill in this form: you will get a case number right away and a confirmation e-mail.

This information is used only to answer your request. Privacy policy