American Wire Gauge (AWG) is the system used in the United States and Canada to identify the size of round electrical conductors. It appears on every wire spool, on terminal markings and on the datasheets of contactors, breakers, terminal blocks and power supplies. This article explains how the gauge is defined, gives a size table computed from the defining formula, and shows how to use resistance values for voltage-drop checks.

How AWG is defined

AWG is a geometric series anchored on two sizes: 4/0 (0000) = 0.4600 in and 36 AWG = 0.0050 in. There are 39 steps between them, and each step changes the diameter by the same ratio. The diameter of gauge n is therefore:

d(n) = 0.127 mm × 92^((36 − n) / 39)

For the "aught" sizes, use n = 0 for 1/0, −1 for 2/0, −2 for 3/0 and −3 for 4/0. A few practical consequences follow directly from the formula:

  • A larger gauge number means a smaller wire.
  • Each gauge step changes the diameter by a factor of about 1.1229.
  • Every 6 gauges, the diameter roughly doubles (factor 2.005).
  • Every 3 gauges, the cross-sectional area roughly doubles, and the resistance per length roughly halves.
  • Every 10 gauges, the area changes by a factor of about 10.2.

Sizes larger than 4/0 are not given gauge numbers. They are specified by area in thousands of circular mils (kcmil, formerly written MCM), for example 250 kcmil. One circular mil is the area of a circle 0.001 in (one mil) in diameter, so the area of a round conductor in circular mils is simply its diameter in mils, squared.

AWG conductor cross-sections from 24 AWG to 4/0 drawn to the same scale, each labelled with its diameter in millimetres and cross-section in square millimetres, from 0.51 mm (0.20 mm²) for 24 AWG to 11.68 mm (107.2 mm²) for 4/0.

AWG diameters to scale, computed from the AWG definition.

AWG size table (4/0 to 30 AWG)

AWG Diameter (in) Diameter (mm) Area (mm²) Area (circular mils) Copper resistance (Ω/km) Copper resistance (Ω/1000 ft)
4/0 0.4600 11.684 107.219 211,600 0.161 0.0490
3/0 0.4096 10.405 85.029 167,806 0.203 0.0618
2/0 0.3648 9.266 67.431 133,077 0.256 0.0779
1/0 0.3249 8.251 53.475 105,535 0.322 0.0983
1 0.2893 7.348 42.408 83,693 0.407 0.1239
2 0.2576 6.544 33.631 66,371 0.513 0.1563
3 0.2294 5.827 26.670 52,635 0.646 0.1970
4 0.2043 5.189 21.151 41,741 0.815 0.2485
5 0.1819 4.621 16.773 33,102 1.028 0.3133
6 0.1620 4.115 13.302 26,251 1.296 0.3951
7 0.1443 3.665 10.549 20,818 1.634 0.4982
8 0.1285 3.264 8.366 16,510 2.061 0.6282
9 0.1144 2.906 6.634 13,093 2.599 0.7921
10 0.1019 2.588 5.261 10,383 3.277 0.9988
11 0.0907 2.305 4.172 8,234 4.132 1.2595
12 0.0808 2.053 3.309 6,530 5.211 1.5882
13 0.0720 1.828 2.624 5,178 6.571 2.0027
14 0.0641 1.628 2.081 4,107 8.285 2.5254
15 0.0571 1.450 1.650 3,257 10.448 3.1844
16 0.0508 1.291 1.309 2,583 13.174 4.0155
17 0.0453 1.150 1.038 2,048 16.612 5.0634
18 0.0403 1.024 0.823 1,624 20.948 6.3849
19 0.0359 0.912 0.653 1,288 26.415 8.0512
20 0.0320 0.812 0.518 1,022 33.308 10.1524
21 0.0285 0.723 0.410 810 42.001 12.8019
22 0.0253 0.644 0.326 642 52.962 16.1429
23 0.0226 0.573 0.258 509 66.784 20.3558
24 0.0201 0.511 0.205 404 84.213 25.6682
25 0.0179 0.455 0.162 320 106.191 32.3670
26 0.0159 0.405 0.129 254 133.904 40.8140
27 0.0142 0.361 0.102 202 168.850 51.4655
28 0.0126 0.321 0.081 160 212.916 64.8968
29 0.0113 0.286 0.064 127 268.482 81.8334
30 0.0100 0.255 0.051 101 338.550 103.1900

Values for guidance, computed from the AWG definition for a solid round conductor. Resistance is for annealed copper at 20 °C (resistivity 1.7241 × 10⁻⁸ Ω·m, 100 % IACS), direct current.

Notes on the table

  • Stranded wire of the same gauge has about the same copper area, but a larger overall diameter and slightly higher resistance because the strands are twisted. For exact values, use the manufacturer's data or the conductor properties table of the electrical code (NEC Chapter 9, Table 8).
  • Temperature raises copper resistance by roughly 0.39 % per °C. At a conductor temperature of 75 °C, resistance is about 1.22 times the 20 °C value.
  • Aluminum conductors have a higher resistivity than copper, so an aluminum conductor needs a larger size to carry the same current with the same losses.
  • Alternating current in large conductors also has a small extra resistance due to skin effect; for the control and branch circuit sizes common in panels, the DC values above are a good approximation at 60 Hz.
Chart of American Wire Gauge (AWG) conductor sizes

Using resistance to estimate voltage drop

For a two-wire circuit, the voltage drop is the current multiplied by the resistance of both conductors (the outgoing and the return path):

Voltage drop = I × R per length × 2 × one-way length

  • Example 1: 12 AWG copper, 100 ft one way, 10 A. Drop ≈ 3.18 V at 20 °C, which is about 2.6 % of 120 V.
  • Example 2: 18 AWG copper, 50 m one way to a sensor or valve on a 24 V DC circuit, 0.5 A. Drop ≈ 1.05 V at 20 °C, about 4.4 % of 24 V.

The second example is typical of long control runs: a 24 V DC device far from its power supply can see noticeably less voltage than the supply delivers, especially when the conductors are warm or several loads share them. Three-phase circuits use a different multiplier; follow the method in your design guide or electrical code.

Why this table has no ampacity column

Ampacity, the current a conductor may carry continuously, is not a property of the copper alone. It depends on:

  • the temperature rating of the insulation (for example 60 °C, 75 °C or 90 °C);
  • the temperature rating of the terminals the wire connects to;
  • the installation method: free air, cable, conduit, raceway or cable tray;
  • the number of current-carrying conductors grouped together and the ambient temperature;
  • specific rules for small conductors, motor circuits, control circuits and machinery.

The values you may use are set by the ampacity tables and adjustment rules of the electrical code (NEC Article 310 in the United States, CEC Section 4 in Canada) and, for machines and panels, by NFPA 79 or UL 508A. Take ampacity from those sources, never from a generic size chart.

Comparing AWG with metric (mm²) sizes

IEC equipment is often specified in square millimeters. Metric and AWG sizes do not line up exactly, so a metric size always falls between two AWG sizes:

Metric size Next smaller even AWG Next larger even AWG
0.5 mm² 22 AWG (0.33 mm²) 20 AWG (0.52 mm²)
0.75 mm² 20 AWG (0.52 mm²) 18 AWG (0.82 mm²)
1 mm² 18 AWG (0.82 mm²) 16 AWG (1.31 mm²)
1.5 mm² 16 AWG (1.31 mm²) 14 AWG (2.08 mm²)
2.5 mm² 14 AWG (2.08 mm²) 12 AWG (3.31 mm²)
4 mm² 12 AWG (3.31 mm²) 10 AWG (5.26 mm²)
6 mm² 10 AWG (5.26 mm²) 8 AWG (8.37 mm²)
10 mm² 8 AWG (8.37 mm²) 6 AWG (13.30 mm²)
16 mm² 6 AWG (13.30 mm²) 4 AWG (21.15 mm²)
25 mm² 4 AWG (21.15 mm²) 2 AWG (33.63 mm²)

Values for guidance, computed from the AWG definition. Odd gauges exist but are rarely used for building and panel wire.

When a terminal is marked in both systems, follow the range printed on the device or in its datasheet, and use the tightening torque given by the manufacturer. Fine-stranded conductors may need ferrules or terminals approved for that conductor class.

Work on electrical equipment must be done by qualified personnel following the applicable electrical code and the manufacturer's instructions.

Key takeaways

  • AWG is a geometric series between 4/0 (0.4600 in) and 36 AWG (0.0050 in) with 39 equal-ratio steps.
  • Three gauges smaller doubles the area and halves the resistance; six gauges smaller doubles the diameter.
  • Sizes above 4/0 are given in kcmil.
  • Use the resistance column for voltage-drop estimates, corrected for temperature.
  • Take ampacity only from the applicable code tables, which depend on insulation, terminals and installation.